← Backflow review queue
Backflow assembly test · 5850 Mill Creek Rd
ApprovedFiled Nov 1, 2025 by Sam Nguyen, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Nov 1, 2025
- Assembly type
- RP
- Serial number
- W125766
- Size
- 3/4
- Test gauge serial
- G-2332
- Gauge calibration date
- Feb 12, 2025
- Check valve 1
- 5.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.2 psid
- Relief valve opened at
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 009-94-01084
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.