Backflow assembly test · 5850 Mill Creek Rd
ApprovedFiled Oct 24, 2024 by Quinn Fairley, Lakeside Backflow Testing · filed from phone
Report
- Date of service
- Oct 24, 2024
- Assembly type
- RP
- Serial number
- W125766
- Size
- 3/4
- Test gauge serial
- G-8092
- Gauge calibration date
- Aug 25, 2024
- Check valve 1
- 5.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.2 psid
- Relief valve opened at
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 009-94-01084
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.