Backflow assembly test · 6771 Cedar Hollow Dr
ApprovedFiled Jul 13, 2025 by Quinn Fairley, Lakeside Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Jul 13, 2025
- Assembly type
- RP
- Serial number
- K348772
- Size
- 1
- Test gauge serial
- G-3815
- Gauge calibration date
- Jun 1, 2024
- Check valve 1
- 0.4 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.5 psid
- Relief valve opened at
- 3.1 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 009-52-01114
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.