Backflow assembly test · Maple Leaf Apartments
ApprovedFiled Mar 29, 2026 by Shawn Hollins, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Mar 29, 2026
- Assembly type
- RP
- Serial number
- W584363
- Size
- 1 1/2
- Test gauge serial
- G-2862
- Gauge calibration date
- Jul 27, 2025
- Check valve 1
- 6.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Relief valve opened at
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 009-19-01145
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.