Backflow assembly test · Corner Market
ApprovedFiled Mar 13, 2026 by Shawn Pruitt, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Mar 13, 2026
- Assembly type
- RP
- Serial number
- B603160
- Size
- 4
- Test gauge serial
- G-6985
- Gauge calibration date
- Dec 29, 2024
- Check valve 1
- 0.8 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.2 psid
- Relief valve opened at
- 3 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 009-69-01291
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
949 Quarry Ln
Owner: Stroud Holdings LLC
Parcel 009-69-01291