Brevard County, FLCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Blue Heron Dental

Approved

Filed Jul 12, 2026 by Shawn Kessler, Valley Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Jul 12, 2026
Assembly type
DC
Serial number
Z430036
Size
1
Test gauge serial
G-5892
Gauge calibration date
Oct 2, 2025
Check valve 1
6.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 009-71-01049
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6876 Cedar Hollow Rd
Owner: Calloway Holdings LLC
Parcel 009-71-01049