Brevard County, FLCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 1725 Meadow Lark Trl

Approved

Filed Oct 14, 2025 by Shawn Kessler, Valley Plumbing & Backflow · filed from phone

Report

Date of service
Oct 14, 2025
Assembly type
RP
Serial number
A836724
Size
1
Test gauge serial
G-2953
Gauge calibration date
May 23, 2025
Check valve 1
4.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 009-15-01266
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1725 Meadow Lark Trl
Owner: Hayden Marsh
Parcel 009-15-01266