Backflow assembly test · Blue Heron Grill
ApprovedFiled May 7, 2024 by Sam Nguyen, Keystone Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- May 7, 2024
- Assembly type
- RP
- Serial number
- K890881
- Size
- 2
- Test gauge serial
- G-9556
- Gauge calibration date
- Oct 13, 2023
- Check valve 1
- 3.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.3 psid
- Relief valve opened at
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 009-69-01160
- Readings in range, no flags
- Result: passing. Next due date resets when approved.