← Backflow review queue
Backflow assembly test · 7551 Quarry Ct
ApprovedFiled May 14, 2024 by Reese Danner, Heritage Plumbing & Backflow · filed from phone
Report
- Date of service
- May 14, 2024
- Assembly type
- RP
- Serial number
- A690846
- Size
- 3/4
- Test gauge serial
- G-5516
- Gauge calibration date
- Sep 3, 2023
- Check valve 1
- 6.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.3 psid
- Relief valve opened at
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-36-01268
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
7551 Quarry Ct
Owner: Alex Ellery
Parcel 001-36-01268