← Backflow review queue
Backflow assembly test · 7551 Quarry Ct
ApprovedFiled Apr 28, 2023 by Morgan Fairley, Evergreen Backflow Testing · filed from phone
Report
- Date of service
- Apr 28, 2023
- Assembly type
- RP
- Serial number
- A690846
- Size
- 3/4
- Test gauge serial
- G-8425
- Gauge calibration date
- Feb 27, 2023
- Check valve 1
- 3.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Relief valve opened at
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-36-01268
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7551 Quarry Ct
Owner: Alex Ellery
Parcel 001-36-01268