← Backflow review queue
Backflow assembly test · Main Street Elementary School
Needs reviewFiled Nov 15, 2026 by Jamie Hollins, Summit Backflow Testing · filed from phone
Report
- Date of service
- Nov 15, 2026
- Assembly type
- RP
- Serial number
- B945013
- Size
- 2
- Test gauge serial
- G-7442
- Gauge calibration date
- Jun 8, 2026
- Check valve 1
- 8.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Relief valve opened at
- 2.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-83-01151
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
5946 Orchard Way
Owner: Whitcomb Holdings LLC
Parcel 001-83-01151