Alachua County, FLCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 1937 Fox Run Rd

Approved

Filed May 22, 2026 by Reese Danner, Heritage Plumbing & Backflow · filed from phone

Report

Date of service
May 22, 2026
Assembly type
RP
Serial number
Z343134
Size
1
Test gauge serial
G-8311
Gauge calibration date
Feb 26, 2026
Check valve 1
7.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-75-01007
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1937 Fox Run Rd
Owner: Emerson Marsh
Parcel 001-75-01007