Alachua County, FLCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 7874 Stone Gate Rd

Approved

Filed Feb 26, 2026 by Rowan Harlow, Evergreen Backflow Testing · filed from phone

Report

Date of service
Feb 26, 2026
Assembly type
RP
Serial number
W810241
Size
1
Test gauge serial
G-1871
Gauge calibration date
Dec 22, 2025
Check valve 1
7.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-83-01104
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7874 Stone Gate Rd
Owner: Parker Benton
Parcel 001-83-01104