← Backflow review queue
Backflow assembly test · Hilltop Animal Hospital
ApprovedFiled Nov 16, 2024 by Jamie Hollins, Summit Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Nov 16, 2024
- Assembly type
- RP
- Serial number
- W988572
- Size
- 1
- Test gauge serial
- G-2449
- Gauge calibration date
- Jun 22, 2024
- Check valve 1
- 5.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.3 psid
- Relief valve opened at
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-16-01124
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
1647 Ridgeview Trl
Owner: Wexler Holdings LLC
Parcel 001-16-01124