Backflow assembly test · Blue Heron Diner
ApprovedFiled Apr 9, 2025 by Jamie Wexler, Summit Backflow Testing · filed from phone
Report
- Date of service
- Apr 9, 2025
- Assembly type
- RP
- Serial number
- K227120
- Size
- 4
- Test gauge serial
- G-4869
- Gauge calibration date
- Nov 26, 2024
- Check valve 1
- 7.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.8 psid
- Relief valve opened at
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-51-01135
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.