Sussex County, DECompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 4707 Quarry Ct

Approved

Filed Jan 9, 2025 by Cameron Lindqvist, Heritage Plumbing & Backflow · filed from phone

Report

Date of service
Jan 9, 2025
Assembly type
RP
Serial number
Z594454
Size
1
Test gauge serial
G-8680
Gauge calibration date
Feb 17, 2024
Check valve 1
7.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Relief valve opened at
1.7 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 005-45-01026
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4707 Quarry Ct
Owner: Parker Nguyen
Parcel 005-45-01026