Sussex County, DECompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Corner Taqueria

Approved

Filed Aug 26, 2026 by Cameron Lindqvist, Heritage Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Aug 26, 2026
Assembly type
DC
Serial number
K601268
Size
1 1/2
Test gauge serial
G-4814
Gauge calibration date
May 17, 2026
Check valve 1
8.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 005-75-01300
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

1850 Ridgeview Dr
Owner: Nguyen Holdings LLC
Parcel 005-75-01300