Backflow assembly test · Corner Taqueria

Approved

Filed Sep 2, 2024 by Alex Calloway, Ridge Plumbing & Backflow · filed from phone

Report

Date of service
Sep 2, 2024
Assembly type
DC
Serial number
K601268
Size
1 1/2
Test gauge serial
G-5988
Gauge calibration date
Dec 7, 2023
Check valve 1
8.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 005-75-01300
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.