Backflow assembly test · 1891 Stone Gate Trl
ApprovedFiled May 24, 2025 by Parker Ramirez, Heritage Plumbing & Backflow · filed from phone
Report
- Date of service
- May 24, 2025
- Assembly type
- DC
- Serial number
- W528924
- Size
- 3/4
- Test gauge serial
- G-8279
- Gauge calibration date
- Dec 26, 2024
- Check valve 1
- 0.3 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.5 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 005-91-01315
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
1891 Stone Gate Trl
Owner: Avery Whitcomb
Parcel 005-91-01315