Sussex County, DECompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 9724 Turkey Hill Dr

Approved

Filed Mar 3, 2026 by Parker Ramirez, Heritage Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Mar 3, 2026
Assembly type
RP
Serial number
K643216
Size
3/4
Test gauge serial
G-6725
Gauge calibration date
Jun 12, 2025
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 005-78-01329
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9724 Turkey Hill Dr
Owner: Morgan Pruitt
Parcel 005-78-01329