Backflow assembly test · 7051 Orchard Rd
ApprovedFiled Feb 6, 2025 by Alex Ellery, Patriot Backflow Testing · filed from phone
Report
- Date of service
- Feb 6, 2025
- Assembly type
- PVB
- Serial number
- A222034
- Size
- 1
- Test gauge serial
- G-5504
- Gauge calibration date
- Nov 18, 2023
- Check valve 1
- 7.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.5 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 005-27-01344
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
7051 Orchard Rd
Owner: Jordan Ramirez
Parcel 005-27-01344