Sussex County, DECompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 2568 Orchard Dr

Approved

Filed Jan 16, 2026 by Alex Ellery, Patriot Backflow Testing · filed from phone

Report

Date of service
Jan 16, 2026
Assembly type
DC
Serial number
Z821319
Size
1
Test gauge serial
G-4786
Gauge calibration date
May 29, 2025
Check valve 1
8.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 005-90-01055
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

2568 Orchard Dr
Owner: Jamie Stroud
Parcel 005-90-01055