Sussex County, DECompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Maple Leaf Bakery

Approved

Filed Aug 5, 2025 by Jordan Ellery, Patriot Backflow Testing · filed from phone

Report

Date of service
Aug 5, 2025
Assembly type
RP
Serial number
A408283
Size
1 1/2
Test gauge serial
G-8711
Gauge calibration date
Dec 29, 2024
Check valve 1
7.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 005-58-01234
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

631 Fox Run Ct
Owner: Ellery Holdings LLC
Parcel 005-58-01234