New Castle County, DECompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 7678 Orchard Dr

Approved

Filed Apr 26, 2025 by Drew Lindqvist, Ridge Backflow Testing · filed from phone

Report

Date of service
Apr 26, 2025
Assembly type
RP
Serial number
W584081
Size
3/4
Test gauge serial
G-9567
Gauge calibration date
Oct 25, 2024
Check valve 1
7.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 003-52-01190
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

7678 Orchard Dr
Owner: Riley Ramirez
Parcel 003-52-01190