← Backflow review queue
Backflow assembly test · Blue Heron Market
ApprovedFiled Jul 8, 2026 by Reese Vance, Valley Backflow Testing · filed from phone
Report
- Date of service
- Jul 8, 2026
- Assembly type
- RP
- Serial number
- K717582
- Size
- 2
- Test gauge serial
- G-2426
- Gauge calibration date
- Oct 3, 2025
- Check valve 1
- 5.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 003-69-01200
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
8892 Sycamore Ln
Owner: Benton Holdings LLC
Parcel 003-69-01200