Backflow assembly test · Crossroads Grill
ApprovedFiled Nov 12, 2025 by Blake Vance, Valley Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Nov 12, 2025
- Assembly type
- RP
- Serial number
- W443827
- Size
- 4
- Test gauge serial
- G-3034
- Gauge calibration date
- Aug 5, 2024
- Check valve 1
- 6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.6 psid
- Relief valve opened at
- 1.2 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 003-37-01103
- RP relief valve must open at 2.0 psid or more.
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
2851 Meadow Lark Dr
Owner: Wexler Holdings LLC
Parcel 003-37-01103