Backflow assembly test · Crossroads Grill

Approved

Filed Nov 12, 2025 by Blake Vance, Valley Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Nov 12, 2025
Assembly type
RP
Serial number
W443827
Size
4
Test gauge serial
G-3034
Gauge calibration date
Aug 5, 2024
Check valve 1
6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Relief valve opened at
1.2 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 003-37-01103
  • RP relief valve must open at 2.0 psid or more.
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

2851 Meadow Lark Dr
Owner: Wexler Holdings LLC
Parcel 003-37-01103