Backflow assembly test · Golden Medical Offices
ApprovedFiled Nov 21, 2024 by Blake Vance, Valley Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Nov 21, 2024
- Assembly type
- RP
- Serial number
- W758093
- Size
- 4
- Test gauge serial
- G-4052
- Gauge calibration date
- Mar 21, 2024
- Check valve 1
- 6.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 003-47-01180
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.