New Castle County, DECompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Station Car Wash

Approved

Filed Aug 26, 2026 by Blake Harlow, Ridge Backflow Testing · filed from phone

Report

Date of service
Aug 26, 2026
Assembly type
RP
Serial number
Z220956
Size
2
Test gauge serial
G-2010
Gauge calibration date
Oct 22, 2025
Check valve 1
8.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Relief valve opened at
1.2 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 003-93-01089
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

6030 Orchard Dr
Owner: Stroud Holdings LLC
Parcel 003-93-01089