Backflow assembly test · Riverside Self Storage

Filed Nov 24, 2026 by Blake Vance, Valley Backflow Testing · filed from phone

Report

Date of service
Nov 24, 2026
Assembly type
RP
Serial number
A570025
Size
1 1/2
Test gauge serial
G-3201
Gauge calibration date
Mar 29, 2026
Check valve 1
8.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 003-97-01167
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Property

4176 Meadow Lark Dr
Owner: Whitcomb Holdings LLC
Parcel 003-97-01167