New Castle County, DECompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 6554 Ridgeview Rd

Approved

Filed Jul 13, 2024 by Blake Vance, Valley Backflow Testing · filed from phone

Report

Date of service
Jul 13, 2024
Assembly type
RP
Serial number
W670148
Size
1
Test gauge serial
G-8476
Gauge calibration date
Sep 19, 2023
Check valve 1
7.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 003-44-01237
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

6554 Ridgeview Rd
Owner: Drew Kessler
Parcel 003-44-01237