Backflow assembly test · Hilltop Medical Offices
Needs reviewFiled Nov 20, 2026 by Reese Vance, Valley Backflow Testing · filed from phone
Report
- Date of service
- Nov 20, 2026
- Assembly type
- DC
- Serial number
- Z736238
- Size
- 4
- Test gauge serial
- G-4321
- Gauge calibration date
- May 22, 2026
- Check valve 1
- 5.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 003-22-01019
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
2232 Pine Knoll Rd
Owner: Pruitt Holdings LLC
Parcel 003-22-01019