Backflow assembly test · 3633 Meadow Lark Ct
ApprovedFiled Oct 23, 2024 by Logan Ramirez, Ridge Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Oct 23, 2024
- Assembly type
- PVB
- Serial number
- A712446
- Size
- 3/4
- Test gauge serial
- G-4451
- Gauge calibration date
- Apr 13, 2024
- Check valve 1
- 7.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.5 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-16-01263
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.