Backflow assembly test · 6039 Cedar Hollow Rd
ApprovedFiled Dec 2, 2025 by Avery Hollins, Ridge Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Dec 2, 2025
- Assembly type
- DC
- Serial number
- K275915
- Size
- 3/4
- Test gauge serial
- G-4617
- Gauge calibration date
- Jan 5, 2025
- Check valve 1
- 8.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.6 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-74-01357
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
6039 Cedar Hollow Rd
Owner: Jamie Ellery
Parcel 001-74-01357