Backflow assembly test · 9184 Turkey Hill Way
ApprovedFiled Jul 15, 2026 by Casey Fairley, Ridge Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Jul 15, 2026
- Assembly type
- DC
- Serial number
- K385952
- Size
- 1
- Test gauge serial
- G-3035
- Gauge calibration date
- Apr 12, 2025
- Check valve 1
- 0.1 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.9 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-43-01085
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
9184 Turkey Hill Way
Owner: Taylor Harlow
Parcel 001-43-01085