← Backflow review queue

Backflow assembly test · 3379 Cedar Hollow Ct

Approved

Filed Sep 10, 2026 by Alex Okafor, Keystone Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Sep 10, 2026
Assembly type
RP
Serial number
B908178
Size
3/4
Test gauge serial
G-8885
Gauge calibration date
Dec 21, 2025
Check valve 1
6.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
1.3 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-31-01063
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.