Kent County, DECompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Crossroads Bakery

Approved

Filed Dec 19, 2025 by Alex Okafor, Keystone Backflow Testing · filed from phone

Report

Date of service
Dec 19, 2025
Assembly type
RP
Serial number
B979960
Size
2
Test gauge serial
G-1710
Gauge calibration date
Jun 22, 2025
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-83-01225
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9012 Sycamore Dr
Owner: Calloway Holdings LLC
Parcel 001-83-01225