Backflow assembly test · 6258 Mill Creek Trl
ApprovedFiled Mar 9, 2025 by Casey Fairley, Ridge Plumbing & Backflow · filed from phone
Report
- Date of service
- Mar 9, 2025
- Assembly type
- DC
- Serial number
- K173855
- Size
- 1
- Test gauge serial
- G-6302
- Gauge calibration date
- Oct 17, 2024
- Check valve 1
- 7.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.2 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-97-01146
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
6258 Mill Creek Trl
Owner: Morgan Ramirez
Parcel 001-97-01146