Backflow assembly test · 3485 Cedar Hollow Rd

Approved

Filed Jun 25, 2026 by Alex Okafor, Keystone Backflow Testing · filed from phone

Report

Date of service
Jun 25, 2026
Assembly type
PVB
Serial number
K143933
Size
3/4
Test gauge serial
G-1591
Gauge calibration date
May 2, 2025
Check valve 1
0.3 psid
Check valve 1 closed tight
No
Check valve 2
3.7 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-80-01249
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.