Weld County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Station Bakery

Approved

Filed Apr 18, 2024 by Blake Hollins, Evergreen Plumbing & Backflow · filed from phone

Report

Date of service
Apr 18, 2024
Assembly type
RP
Serial number
W237434
Size
1
Test gauge serial
G-8381
Gauge calibration date
Feb 26, 2024
Check valve 1
7.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
1.5 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 123-78-01294
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

2951 Turkey Hill Ct
Owner: Ashby Holdings LLC
Parcel 123-78-01294