Backflow assembly test · Station Bakery
ApprovedFiled Apr 18, 2024 by Blake Hollins, Evergreen Plumbing & Backflow · filed from phone
Report
- Date of service
- Apr 18, 2024
- Assembly type
- RP
- Serial number
- W237434
- Size
- 1
- Test gauge serial
- G-8381
- Gauge calibration date
- Feb 26, 2024
- Check valve 1
- 7.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.2 psid
- Relief valve opened at
- 1.5 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 123-78-01294
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.