← Backflow review queue
Backflow assembly test · 7809 Hickory Ln
ApprovedFiled Aug 1, 2023 by Blake Hollins, Evergreen Plumbing & Backflow · filed from phone
Report
- Date of service
- Aug 1, 2023
- Assembly type
- PVB
- Serial number
- W154108
- Size
- 1
- Test gauge serial
- G-2263
- Gauge calibration date
- Jan 21, 2023
- Check valve 1
- 5.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 123-98-01169
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7809 Hickory Ln
Owner: Logan Nguyen
Parcel 123-98-01169