Weld County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 4241 Meadow Lark Dr

Approved

Filed Nov 11, 2025 by Blake Hollins, Evergreen Plumbing & Backflow · filed from phone

Report

Date of service
Nov 11, 2025
Assembly type
RP
Serial number
K828315
Size
1
Test gauge serial
G-7568
Gauge calibration date
May 18, 2025
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 123-56-01068
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4241 Meadow Lark Dr
Owner: Hayden Brandt
Parcel 123-56-01068