Backflow assembly test · 646 Meadow Lark Rd
ApprovedFiled Jan 10, 2024 by Blake Hollins, Evergreen Plumbing & Backflow · filed from phone
Report
- Date of service
- Jan 10, 2024
- Assembly type
- DC
- Serial number
- K180280
- Size
- 1
- Test gauge serial
- G-8968
- Gauge calibration date
- Jul 12, 2023
- Check valve 1
- 6.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.5 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 123-84-01332
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.