← Backflow review queue
Backflow assembly test · Blue Heron Elementary School
ApprovedFiled Apr 30, 2025 by Taylor Wexler, Lakeside Plumbing & Backflow · filed from phone
Report
- Date of service
- Apr 30, 2025
- Assembly type
- RP
- Serial number
- B529198
- Size
- 1
- Test gauge serial
- G-7117
- Gauge calibration date
- Dec 9, 2024
- Check valve 1
- 4.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Relief valve opened at
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 123-88-01276
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
7757 Stone Gate Dr
Owner: Nguyen Holdings LLC
Parcel 123-88-01276