Weld County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Blue Heron Elementary School

Approved

Filed Apr 30, 2025 by Taylor Wexler, Lakeside Plumbing & Backflow · filed from phone

Report

Date of service
Apr 30, 2025
Assembly type
RP
Serial number
B529198
Size
1
Test gauge serial
G-7117
Gauge calibration date
Dec 9, 2024
Check valve 1
4.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 123-88-01276
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

7757 Stone Gate Dr
Owner: Nguyen Holdings LLC
Parcel 123-88-01276