Summit County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 2873 Stone Gate Trl

Approved

Filed Dec 22, 2024 by Avery Fairley, Summit Plumbing & Backflow · filed from phone

Report

Date of service
Dec 22, 2024
Assembly type
PVB
Serial number
Z713301
Size
1
Test gauge serial
G-9150
Gauge calibration date
Oct 28, 2023
Check valve 1
0.2 psid
Check valve 1 closed tight
No
Check valve 2
2.6 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 117-90-01005
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2873 Stone Gate Trl
Owner: Logan Danner
Parcel 117-90-01005