Summit County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Golden Grill

Approved

Filed Jan 6, 2026 by Jamie Hollins, Ridge Plumbing & Backflow · filed from phone

Report

Date of service
Jan 6, 2026
Assembly type
RP
Serial number
A246285
Size
1 1/2
Test gauge serial
G-8254
Gauge calibration date
Jul 31, 2025
Check valve 1
3.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Relief valve opened at
1.1 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 117-23-01124
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7015 Old Church Ln
Owner: Whitcomb Holdings LLC
Parcel 117-23-01124