Summit County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 6536 Sycamore Dr

Approved

Filed Oct 31, 2026 by Riley Pruitt, Ridge Backflow Testing · filed from phone

Report

Date of service
Oct 31, 2026
Assembly type
RP
Serial number
W522838
Size
3/4
Test gauge serial
G-6396
Gauge calibration date
Dec 27, 2025
Check valve 1
8.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
1.6 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 117-49-01058
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.