Backflow assembly test · 6506 Sycamore Ln

Approved

Filed Jul 30, 2024 by Alex Whitcomb, Ridge Backflow Testing · filed from phone

Report

Date of service
Jul 30, 2024
Assembly type
RP
Serial number
Z574969
Size
3/4
Test gauge serial
G-2543
Gauge calibration date
Apr 7, 2024
Check valve 1
7.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 117-78-01041
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6506 Sycamore Ln
Owner: Drew Brandt
Parcel 117-78-01041