Summit County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Crossroads Dental

Approved

Filed Jul 31, 2025 by Riley Pruitt, Ridge Backflow Testing · filed from phone

Report

Date of service
Jul 31, 2025
Assembly type
RP
Serial number
W126624
Size
1
Test gauge serial
G-4622
Gauge calibration date
Nov 11, 2024
Check valve 1
3.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 117-47-01127
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

5913 Hickory Way
Owner: Okafor Holdings LLC
Parcel 117-47-01127