Backflow assembly test · 4556 Fox Run Way
ApprovedFiled Nov 2, 2023 by Riley Pruitt, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Nov 2, 2023
- Assembly type
- RP
- Serial number
- W689061
- Size
- 1
- Test gauge serial
- G-1161
- Gauge calibration date
- Aug 13, 2023
- Check valve 1
- 7.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2 psid
- Relief valve opened at
- 2.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 117-67-01277
- Readings in range, no flags
- Result: passing. Next due date resets when approved.