← Backflow review queue
Backflow assembly test · 8710 Fox Run Trl
ApprovedFiled Oct 16, 2025 by Avery Fairley, Summit Plumbing & Backflow · filed from phone
Report
- Date of service
- Oct 16, 2025
- Assembly type
- RP
- Serial number
- Z474923
- Size
- 1
- Test gauge serial
- G-5504
- Gauge calibration date
- Dec 31, 2024
- Check valve 1
- 8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 4 psid
- Relief valve opened at
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 117-79-01071
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
8710 Fox Run Trl
Owner: Parker Brandt
Parcel 117-79-01071